Gel battery is different from AGM VRLA battery, which uses the gel electrolyte, allowing you to mount the battery in any direction, even upside down, giving more flexibility to installers.
A gel cell is a “recombinant” battery. This means that the oxygen that is normally produced on the positive plate in all lead acid batteries recombines with the hydrogen given off by the negative plate. The “recombination” of hydrogen and oxygen produces water (H which replaces the moisture in the battery. Therefore, the battery is maintenance-free, as it never needs watering.
The oxygen is trapped in the cell by special pressurized sealing vents. It travels to the negative plate through tiny fissures or cracks in the gelled electrolyte.
The sealing vent is critical to the performance of the gel cell. The cell must maintain a positive internal pressure. Otherwise the recombination of the gasses will not take place, and the cell will dry out and not perform.
In addition, the valve must safely release any excess pressure that may be produced during overcharging. Otherwise the cell would be irreparably damaged.
It’s important to note that a gel cell must never be opened once it leaves the factory. If opened, the cell loses its pressure, and the outside air will “poison” the plates and cause an imbalance that destroys the recombination chemistry.
If you want to know more about gel battery, you can just visit Leoch International, which is an excellent manufacturer of lead acid battery. The company is a public company which has over 10 year’s history and it is very reliable and dependable. If you are interested in the company, you can search for more information in the internet. The office website is http://www.leoch.com.